Loading...
3 - 22 3 - 22
MELSEC-Q
3 SPECIFICATIONS
3.4.2 Buffer memory assignment (Q64DAN/Q64DA)
This section describes the assignment of the Q64DAN/Q64DA buffer memory.
POINT
Do not write data from System area or sequence program to the buffer memory
area where writing is disabled. Doing so may cause malfunction.
Table 3.8 Buffer memory assignment (Q64DAN/Q64DA) (1/2)
Address
Description Default
1
Read/write
2
Reference
section
Hexadecimal Decimal
0H 0 D/A conversion enable/disable FH R/W Section 3.4.5
1H 1 CH1 Digital value 0 R/W
Section 3.4.6
2H 2 CH2 Digital value 0 R/W
3H 3 CH3 Digital value 0 R/W
4H 4 CH4 Digital value 0 R/W
5H 5
System area
to to
AH 10
BH 11 CH1 Set value check code 0 R
Section 3.4.7
CH 12 CH2 Set value check code 0 R
DH 13 CH3 Set value check code 0 R
EH 14 CH4 Set value check code 0 R
FH 15
System area
to to
12H 18
13H 19 Error code 0 R/W Section 3.4.8
14H 20 Setting range (CH1 to CH4) 0H R Section 3.4.9
15H 21 System area
16H 22 Offset/gain setting mode Offset specification 0 R/W
Section 3.4.10
17H 23 Offset/gain setting mode Gain specification 0 R/W
18H 24 Offset/gain adjustment value specification 0 R/W Section 3.4.11
19H 25
— —
to to System area
9DH 157
9EH 158
Mode switching setting
0 R/W
Section 3.4.12
9FH 159 0 R/W
A0H 160
— —
to to System area
C7H 199
1 This is the initial value set after the power is turned on or the programmable controller CPU is reset.
2 Indicates whether reading from and writing to a sequence program are enabled.
R : Reading enabled W : Writing enabled