3.4.11 Offset/gain adjustment value specification (buffer memory address 24: Un\G24)
(1) This area is used to set the amount of adjustment for analog output values in the
offset/gain setting mode.
(2) The valid input range is from –3000 to 3000.
When the input value is 1000, the analog output values can be adjusted by about
0.33 V for voltage output and about 0.65 mA for current output.
(3) Refer to Section 4.6 for the details of the offset/gain settings.
3.4.12 Mode switching setting (buffer memory address 158, 159: Un\G158, Un\G159)
(1) Set the values of the mode to which you want to switch.
(2) After setting the values, turning Operating condition setting request (Y9) from off
to on switches to that mode.
(3) When mode switching is performed, this area is cleared to zero and Operating
condition setting completed flag (X9) turns off.
After confirming that Operating condition setting completed flag (X9) has turned
off, turn off Operating condition setting request (Y9).
Mode to be switched to
Set values
Buffer memory address 158 Buffer memory address 159
Normal mode 0964H 4144H
Offset/gain setting mode 4144H 0964H
POINT
If the values written are other than the above, mode switching is not performed and
only the operating condition is changed.