3 - 32 3 - 32
MELSEC-Q
3 SPECIFICATIONS
3.4.13 Pass data classification setting (buffer memory address 200: Un\G200)
(Q62DAN, Q64DAN, Q62DA, and Q64DA only)
(1) Areas used to restore the user range settings offset/gain values when online
module change is made.
Refer to Chapter 7 for details of online module change.
(2) Specify whether the offset/gain values to be saved/restored are voltages or
currents when saving/restoring the offset/gain values of the user range setting.
POINT
Refer to Section 4.6 for the offset/gain value setting method.
b15 b14 b13 b12 b11 b10 b9 b8
b7
b6
b5
b4 b3 b2 b1 b0
CH4 CH3 CH2 CH1
00000000
Q62DAN, Q62DA: Data in b2 to b15 are fixed to 0.
Q64DAN, Q64DA: Data in b4 to b15 are fixed to 0.
1: Current specified
0: Voltage specified
0000