4 SETUP AND PROCEDURES BEFORE OPERATION
4.5 Switch Setting for Intelligent Function Module
The settings for the intelligent function module are performed using the I/O assignment
settings of GX Developer.
(1) Setting item
The intelligent function module switches consist of switches 1 to 5 and are set
using 16 bit data. When the intelligent function module switches are not set, the
default value for switches 1 to 5 is 0.
Table 4.1 Switch setting item for intelligent function module
Setting item
Switch 1
Output range setting
(CH1 to CH4)
Analog output range Output range setting value
4 to 20 mA
0H
1
0 to 20 mA 1H
1 to 5 V 2H
Switch 2
Output range setting
(CH5 to CH8)
0 to 5 V 3
H
– 10 to 10 V 4H
User range setting FH
Switch 3
For the Q62DAN, Q64DAN, Q62DA and Q64DA
HOLD/CLEAR function setting
0
H : CLEAR
1
H to FH (numeric
value other than 0H)
2
: HOLD
For the Q68DAVN, Q68DAIN, Q68DAV and
Q68DAI
HOLD/CLEAR function setting
0 : CLEAR
1 : HOLD
Switch 4
Switch 5 0H: Fixed
1 For details, refer to the POINT(1) in the following page.
2 Setting any value within the setting range will provide the same operation.
When the setting range is 1
H to FH, set 1H for example.
H
CH4CH3CH2CH1
H
CH8CH7CH6CH5
H
CH4CH3CH2CH1
CH8CH7CH6CH5CH4CH3CH2CH1
b7 b6 b5 b4 b3 b2 b1 b0b8
0
b15
0to
H
00
H
01
H
to FF
H
(numeric
value other than 00
H)*
: Normal mode (non-synchronized)
: Synchronized output mode
0
H
1
H
to F
H
(numeric
value other than 0
H
)*
: Normal mode (D/A conversion processing)
: Offset/gain setting mode
0
H
1
H
to F
H
(numeric
value other than 0
H)*
: Normal resolution mode
: High resolution mode
2
2
2