MELSEC-Q
4 SETUP AND PROCEDURES BEFORE OPERATION
(2) Operating procedure
Start the settings with GX Developer I/O assignment setting dialog box.
(a) I/O assignment setting dialog box
Set the following for the slot in which the D/A converter module is mounted.
The type setting is required; set other items as needed.
Type : Select "intelli."
Model name : Enter the module model name.
Points : Select 16 points.
Start XY : Enter the start I/O signal for the D/A converter module.
Detailed setting :
1) When using in the standard system configuration (on the main or
extension base), specify the control CPU of the D/A converter module.
The analog output status of when an error has occurred in the D/A
converter module is determined according to the setting of
"HOLD/CLEAR function setting" of the switch setting for intelligent
function module. Therefore, the setting of "Error time output mode" is
invalid.
2) When using on a remote I/O station, if the analog output is to be held in
the case of a link error, "Error time output mode" must be set to "Hold".