231
CHAPTER 9 CC-LINK IE FIELD NETWORK DIAGNOSTICS
9
9.7 Setting/Canceling Temporary Error Invalid Station
(2) Configuring/canceling the setting in the "Enable/Disable Ignore Station Errors"
window
Temporary error invalid station setting can be configured to multiple slave stations through the "Enable/Disable
Ignore Station Errors" window all at once.
(a) Temporary error invalid station setting
1. Connect GX Works2 to the CPU module.
2. Start the CC-Link IE Field Network diagnostics from
the menu.
[Diagnostics] [CC IE Field Diagnostics]
3. Click the button in the "CC IE
Field Diagnostics" window.
The "Enable/Disable Ignore Station Errors" window
opens.
4. In "Ignore Station Error List", click the number of
the target station. The text turns red and the
background turns yellow.
:
Only stations for which temporary error invalid station
setting has not been configured can be selected
(displayed in white).
5. Clicking the button will temporarily set the
station as an error invalid station.