7 EMC DIRECTIVES
7.1 Requirements for Compliance with the EMC Directive
73
7
Cable clamp
It is also possible to ground the exposed shielded part of the cable to the control panel with the cable clamp.
Ground the shield at a position 20 to 30cm (7.87 to 11.81inch) away from the module.
Cable clamp (Recommended product)
Measure against noise
Refer to the following for details of wiring for the power supply module.
MELSEC iQ-R Module Configuration Manual
When laying an Ethernet cable out from the control panel, ground with a cable clamp etc., at a position 20 to 30cm (7.87 to
11.81inch) from the module.
Refer to peripheral device configuration for details of each cable (Ethernet cable). (Page 17 Peripheral device
configuration)
In wiring inside the panel, the power line connected to the power or servo amplifier and the communication cable such as
bus connection cable or network cable must not be mixed. If the cables are installed closely with each other for wiring
reasons, using a separator (made of metal) can make the cables less influenced by noise. Mixing the power line and
communication cable may cause malfunction due to noise.
Manufacturer Model name
Mitsubishi electric AERSBAN-DSET
AERSBAN-ESET
AD75CK
CAUTION
Do not ground the cable clamp to the top of control panel. Doing so may lead to damage by drop of screws, etc. during installation or removing the cable
clamp.
Motion controller
Inside control panel
AD75CK
20 to 30cm
(7.87 to 11.81inch)