112
3 TROUBLESHOOTING
3.5 List of Alarm Codes
3.5 List of Alarm Codes
If an alarm occurs during operation, the A/D converter module stores the alarm code into 'Latest alarm code' (Un\G2) of the
buffer memory. Turning on 'Error clear request' (YF) clears the alarm code of 'Latest alarm code' (Un\G2).
in alarm codes: This symbol indicates the number of the channel where an alarm has occurred. A numerical value of 0 to F
is used to correspond to CH1 to CH16.
(CH1: 0, CH2: 1, CH3: 2, CH4: 3, CH5: 4, CH6: 5, CH7: 6, CH8: 7, CH9: 8, CH10: 9, CH11: A, CH12: B, CH13: C, CH14: D,
CH15: E, CH16: F)
Alarm code Alarm name Description and cause Corrective Action
080H Process alarm (upper limit) The process alarm (upper limit) has occurred in
CH.
Adjust CH Digital operation value to fall within
the set range. As a result, the corresponding bit of
CH Alert output flag (process alarm upper limit)
or CH Alert output flag (process alarm lower
limit) and 'Alert output signal' (X8) turn off.
081H Process alarm (lower limit) The process alarm (lower limit) has occurred in
CH.
082H Rate alarm (upper limit) The rate alarm (upper limit) has occurred in CH. Adjust the change rate in CH Digital output
value to fall within the set range. As a result, the
corresponding bit of CH Alert output flag (rate
alarm upper limit) or CH Alert output flag (rate
alarm lower limit) and 'Alert output signal' (X8) turn
off.
083H Rate alarm (lower limit) The rate alarm (lower limit) has occurred in CH.
090H Input signal error detection
(upper limit)
An input signal error (upper limit) has been detected
in CH.
The following operations are performed by turning
on and off 'Error clear request' (YF) after the
analog input value returns within the setting range.
All the bits of CH Input signal error detection
flag are set to Normal (0).
'Input signal error detection signal' (XC) turns
off.
'Latest alarm code' (Un\G2) is cleared.
091H Input signal error detection
(lower limit)
An input signal error (lower limit) has been detected
in CH.
0A0H Input signal error detection
(disconnection)
An input signal error (disconnection) has been
detected in CH.