1 FUNCTIONS
1.1 Processing of Each Function
19
1
1.1 Processing of Each Function
The functions are processed in the order shown below. If multiple functions are enabled, the output of the first processed
function is used as the input of the next function.
Digital output value (32 bits)
These values are the digital values after the sampling processing, each averaging processing, or primary delay filter has been
performed.
Digital output value
These values are the 16-bit digital output values that were converted from 32-bit digital output values.
Digital operation value
These values are obtained by operating a digital output value using the digital clipping function, scaling function, shift function,
or difference conversion function. When each function is not used, the same value as the digital output value is stored.
Maximum and minimum value
The maximum and minimum values of the digital operation values are stored.
Logging data
When the logging function is used, digital output values or digital operation values are collected.
CH Digital
output value
CH Maximum
value
CH Minimum
value
CH Digital
operation value
CH Logging
data
Analog input
(CH1 to CH16)
A/D conversion
method
Input signal
error detection
function
Sampling
processing
Count average
Time average
Alert output
function
Moving average
Primary delay
filter
Digital clipping
function
Scaling function
Shift function
Difference
conversion
function
Maximum value/
minimum value
hold function
Logging function
CH Digital
output value
(32 bits)
Rate
alarm
Process
alarm