APPX
Appendix 5 Operation Examples of When the Remote Head Module Is Mounted
209
A
6. Set "Network Configuration Settings" of "Module Parameter" of the master/local module as shown below.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Module Parameter] [Basic Settings]
[Network Configuration Settings]
7. Set "Refresh Setting" of "Module Parameter" of the master/local module as shown below.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Module Parameter] [Basic Settings]
[Refresh Setting]
8. Write the set parameters to the CPU module on the master station. Then reset the CPU module or power off and on the
system.
[Online] [Write to PLC]
For parameters of the master/local module which are not described in this procedure, set default values. For
details on parameters of the master/local module, refer to the following.
MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)