8 SYSTEM CONFIGURATION
8.2 Redundant Line
239
8
(4) CC-Link IE Field Network supporting cable Use cables supporting CC-Link IE Field Network. ( MELSEC iQ-R Ethernet/CC-Link IE User's
Manual (Startup))
(5) Remote head module Use two sets of the RJ72GF15-T2 to build a redundant configuration. Note that the module has
restrictions on use in a system on the system configuration diagram. For details, refer to the
MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual (Application).
(6) Module set Composed of the following modules:
• R60AD8-G (Main)
• R60AD8-G (Sub)
• R60DA8-G for diagnostics
•RY40PT5B
■Precautions
• When using the R60AD8-G in SIL2 mode, there is a restriction on the version. For details, refer to
Page 240 Firmware Version for SIL2 Mode.
• Mount the above modules on the same base. Mount the modules so that they are arranged in the
following order: R60AD8-G (Main) R60AD8-G (Sub) R60DA8-G for diagnostics
RY40PT5B, starting from the right side of the remote head module.
(7) Connector/terminal block converter module for
the R60AD8-G
Use the following products.
Page 240 Connector/terminal block converter module for the R60AD8-G
(8) Connector/terminal block converter module
connection cable for the R60AD8-G
This cable is a special cable for connecting the R60AD8-G and the connector/terminal block
converter module. Use the following products.
Page 240 Connector/terminal block converter module for the R60AD8-G
(9) Connector/terminal block converter module for
the R60DA8-G for diagnostics
Use the following products.
Page 240 Connector/terminal block converter module for the R60DA8-G for diagnostics
(10) Connector/terminal block converter module
connection cable for the R60DA8-G for
diagnostics
This cable is a special cable for connecting the R60DA8-G for diagnostics and the connector/
terminal block converter module. Use the following products.
Page 240 Connector/terminal block converter module for the R60DA8-G for diagnostics
(11) Terminal module for the RY40PT5B This module is used to connect the relay switching RY40PT5B to relays. Use the following products.
Page 240 Terminal module for the RY40PT5B
(12) Terminal module connection cable for the
RY40PT5B
This cable is a special cable for connecting the RY40PT5B and the terminal module. Use the
following products.
Page 240 Terminal module for the RY40PT5B
(13) Relay Use the following products.
Page 240 Relay
No. Name Description