9 INSTALLATION AND WIRING
9.2 External Wiring
245
9
Current input
*1 For the application below, use shielded cables and single point grounding for the shield.
Between the sensor and relay
Between the R60AD8-G and relay
Between the R60DA8-G for diagnostics and relay
*2 Install the relay and programmable controller within the same panel.
*3 When it is necessary to make the R60AD8-G compliant with EMC and Low Voltage Directives, refer to one of the following manuals.
MELSEC iQ-R Module Configuration Manual
Safety Guidelines (This manual is included with the base unit.)
*4 Relay cannot receive 24V output signals and therefore cannot be directly connected to the RY40PT5B.
*5 For details on wiring for relay switching, refer to the following.
Page 247 Relay switching wiring
*6 Use an external power supply that satisfies the following conditions.
The overvoltage protection function is available.
The output voltage does not exceed 35VDC in single fault state.
R60AD8-G(Main)
R60AD8-G(Sub)
RY40PT5B
+
-
+
-
+
-
+
-
V+
I+
V-/I-
V+
I+
I+
V-/I-
V-/I-
24V
24G
Y1
(-)
Y1
(+)
Y0
(-)
Y0
(+)
Cable
*1
Relay
*2
Cable
*1
Cable
*1
Cable
*1
Cable
*3
Cable
*1
Sensor
Sensor
Relay
*2
24VDC
*3*6
Wiring for relay switching
*5
Terminal module
*4
24V
DC
0V
DC
R60DA8-G for diagnostics