246
9 INSTALLATION AND WIRING
9.2 External Wiring
When the connector/terminal block converter module is used
The connector/terminal block converter module and special cable for the R60AD8-G can be used for wiring.
When the connector/terminal block converter module is used, the wiring should be as follows.
*1 Be sure to use a shielded cable. And be sure to ground the shield.
For available connector/terminal block converter modules and special cables, refer to the following.
Page 240 Connector/terminal block converter module for the R60AD8-G
Factory default setting of the R60AD8-G uses the offset/gain setting adjusted per module.
If a connector/terminal block converter module and a special cable are used, they may cause an error on the
conversion characteristics due to effect of conductor resistance.
If the effect of conductor resistance is a problem, set offset and gain values and use the user range setting.
For the offset/gain setting, refer to the following.
MELSEC iQ-R Channel Isolated Analog-Digital Converter Module User's Manual (Startup)
CH1 V+
CH1 V-
*1
Dedicated cable
Shield
*1
Connector/terminal block
converter module