10 FUNCTIONS
10.1 SIL2 Mode
251
10
Module parameters for "R60AD8-G(S2M)"
For details on each parameter, refer to the section of each function.
Module parameters for "R60DA8-G"
Set the following module parameters so that the module operates as the R60DA8-G for diagnostics. For parameters other
than the following, use the default values.
Module parameter Reference
Basic settings A/D conversion enable/disable setting Page 266 A/D Conversion Enable/Disable Setting Function
Input range setting Page 265 Range Switching Function
Averaging process setting Page 266 A/D Conversion Method
Count average/Moving average setting
Transmission interval monitoring time Page 274 SIL2 A/D Conversion Function
Application settings Scaling enable/disable setting Page 269 Scaling Function
Scaling upper limit value
Scaling lower limit value
Digital clipping enable/disable setting Page 272 Digital Clipping Function
SIL2 A/D conversion cycle setting Page 274 SIL2 A/D Conversion Function
Duplex input error range setting Page 281 Double input discrepancy detection function
Duplicated input mismatch detection count
Duplicated input mismatch automatic
recovery setting
Duplicated input mismatch automatic return
count
A/D conversion circuit diagnostic cycle
setting
Page 286 A/D conversion circuit diagnostic function
Module parameter Description
Basic settings Output range setting Set the following value depending on "Input range setting" of "R60AD8-G(S2M)".
For the voltage input range: "-10 to 10V"
For the current input range: "4 to 20mA (Extension)"
D/A conversion enable/disable setting Set "D/A conversion enable" to the same channel number as the A/D conversion enabled
channel number of "R60AD8-G(S2M)".
Application settings Input value shift amount Set the following value depending on "Input range setting" of "R60AD8-G(S2M)".
For the voltage input range: 0
For the current input range: 4000
Auto restore of Offset/ gain setting with the
module change
Do not change the default value. Note that in a SIL2 analog input system, it operates as
"Disable".
Refresh settings Digital value Set W0 to W7 to CH1 to CH8 in ascending order.
Example) CH1: W0, CH2: W1 ... CH7: W6, CH8: W7