268
10 FUNCTIONS
10.5 A/D Conversion Method
Moving average
The A/D converter module averages digital operation values taken at every sampling period for a specified number of times.
The following figure shows the moving average processing of when the set number of times is five.
Setting procedure
Sampling processing
Set "Averaging process specification" to "Sampling processing".
[Navigation window] [Parameter] [Module Information] Module model name [Module Parameter] [Basic
setting] [A/D conversion method]
Averaging processing
1. Set "Averaging process specification" to "Count average" or "Moving average".
[Navigation window] [Parameter] [Module Information] Module model name [Module Parameter] [Basic
setting] [A/D conversion method]
2. Set a value for "Count average/Moving average setting".
digit: Digital operation value
t: Time (ms)
Item Setting range
Count average 4 to 500 (times)
Moving average 2 to 200 (times)
32000
(1)
(2)
(3) (4)
(5)
(6)
(7)
(8) (9)
(10) (11)
(12)
16000
0
0
(a) (b) (c)
(1) + (2) + (3) + (4) + (5)
5
(a)
(2) + (3) + (4) + (5) + (6)
5
(b)
(3) + (4) + (5) + (6) + (7)
5
(c)
t
digit
Value transition in the module
0
3rd storage (c)
2nd storage (b)
1st storage (a)
Sampling cycle
Values in the module