10 FUNCTIONS
10.7 Digital Clipping Function
273
10
Setting example
Ex.
When the following values are used for the R60AD8-G with the input range of 0 to 5V
"Scaling enable/disable setting": "Enable"
"Scaling upper limit value": 12000
"Scaling lower limit value": 2000
"Digitalclip enable/disable setting": "Enable"
When the digital clipping function is used with the scaling function, scale conversion is performed on the value
obtained after digital clipping.
(1) Digital operation value before processing
Digital clipping
-768 to 32767
0 to 32000
(2) Value after digital clipping
Scaling
0 to 32000
2000 to 12000
(3) Digital operation value to be output
Input voltage (V) Digital operation value before processing Digital operation value to be output
-0.12 -768 2000
0 0 2000
1 6400 4000
2 12800 6000
3 19200 8000
4 25600 10000
5 32000 12000
5.096 32767 12000
(2)
(1)
(3)
32000
32767
12000
2000
-768
0
05
Analog input voltage (V)