1 FUNCTIONS
1.5 Scaling Function
27
1
Setting example
Ex.
When 20000 is set to the scaling upper limit value and 4000 is set to the scaling lower limit value for the module with the input
range of 0 to 5V
*1 These values are also applied to the case of digital output values (32 bits).
Ex.
When 20000 is set to the scaling upper limit value and 4000 is set to the scaling lower limit value for the module with the input
range of -10 to 10V
*1 These values are also applied to the case of digital output values (32 bits).
Voltage input (V) Digital output value
*1
Digital operation value
(scaling value)
0 0 4000
1 6400 7200
2 12800 10400
3 19200 13600
4 25600 16800
5 32000 20000
Voltage input (V) Digital output value
*1
Digital operation value
(scaling value)
-10 -32000 4000
-5 -16000 8000
0 0 12000
5 16000 16000
10 32000 20000
32000
0
50
Analog input voltage (V)
Scaling upper limit value 20000
Scaling lower limit value 4000
32000
-32000
10
0
-10
0
Analog input voltage (V)
Scaling upper limit value: 20000
Scaling lower limit value: 4000