28
1 FUNCTIONS
1.5 Scaling Function
When 20000 is set to the scaling upper limit value and 4000 is set to the scaling lower limit value for the module with the input
range of 1 to 5V (extended mode)
*1 Because the value exceeds the range of -32768 to 32767, the value is fixed to 32767 (the upper limit value).
Voltage input (V) Digital output value Digital operation value
(scaling value)
16 bits 32 bits
0 -8000 -8000 0
1004000
2 8000 8000 8000
3 16000 16000 12000
4 24000 24000 16000
5 32000 32000 20000
5.5 32767
*1
36000 22000
32000
36000
0
-8000
5 5.501
Analog input voltage (V)
Scaling upper limit value: 20000
Scaling lower limit value: 4000