1 FUNCTIONS
1.9 Digital Clipping Function
55
1
Setting example
When the following values are used for the A/D converter module with the input range of 0 to 5V
• 'CH1 Scaling enable/disable setting' (Un\G504): Enable (0)
• 'CH1 Scaling upper limit value' (Un\G506): 12000
• 'CH1 Scaling lower limit value' (Un\G508): 2000
• 'CH1 Conversion value shift amount' (Un\G472): 2000
• 'CH1 Digital clipping enable/disable setting' (Un\G510): Enable (0)
*1 These values are also applied to the case of digital output values (32 bits).
When the digital clipping function is used with the scaling function, shift function, and difference conversion
function, scale conversion, shift-and-add, and difference conversion are performed on the value obtained after
digital clipping.
(1) 'CH1 Digital output value' (Un\G400)
Digital clipping
-768 to 32767
0 to 32000
(2) Value after digital clipping
Scaling
0 to 32000
2000 to 12000
(3) Value after scaling
'CH1 Conversion value shift amount' (Un\G472) "+2000"
4000 to 14000
(4) 'CH1 Digital operation value' (Un\G402)
Input voltage (V) Digital output value
*1
Digital operation value
-0.12 -768 4000
0 0 4000
1 6400 6000
2 12800 8000
3 19200 10000
4 25600 12000
5 32000 14000
5.096 32767 14000
(2)
(1)
(3)
(4)
32000
32767
14000
12000
2000
-768
4000
0
05
Analog input voltage (V)