62
1 FUNCTIONS
1.12 Logging Function
■Saving logging data into a CSV file
The data in 'CH1 Logging data' (Un\G10000 to Un\G10999) disappears when the module is powered off. However, the data
can be saved in a CSV file by using function blocks (FBs).
Operation of logging
■Starting logging data collection
Logging data collection starts when 'CH1 Logging enable/disable setting' (Un\G535) is set to Enable (0) and 'Operating
condition setting request' (Y9) is turned on and off.
The data in 'CH1 Digital output value' (Un\G400) or 'CH1 Digital operation value' (Un\G402) is stored in 'CH1 Logging data'
(Un\G10000 to Un\G10999) on the set logging cycle. The data in 'CH1 Digital output value (32 bits)' (Un\G410, Un\G411)
cannot be logged.
■Logging data
Logging data are stored in the following buffer memory areas.
When the number of stored data points is 10001 or greater, the data is overwritten with new data from the head of the storage
area of the corresponding channel.
*1 When the R60AD8-G is used, data is stored in CH1 to CH8.
If logging has been performed even once, all the logging data above are cleared to 0 at the timing when 'Operating condition
setting request' (Y9) is turned off and on.
Logging data setting
Select a data type to be collected with 'CH1 Logging data setting' (Un\G536).
• Digital output value (0)
• Digital operation value (1)
Channel
*1
Storage area for logging data
CH1 Un\G10000 to Un\G10999
CH2 Un\G11000 to Un\G11999
CH3 Un\G12000 to Un\G12999
CH4 Un\G13000 to Un\G13999
CH5 Un\G14000 to Un\G14999
CH6 Un\G15000 to Un\G15999
CH7 Un\G16000 to Un\G16999
CH8 Un\G17000 to Un\G17999
CH9 Un\G18000 to Un\G18999
CH10 Un\G19000 to Un\G19999
CH11 Un\G20000 to Un\G20999
CH12 Un\G21000 to Un\G21999
CH13 Un\G22000 to Un\G22999
CH14 Un\G23000 to Un\G23999
CH15 Un\G24000 to Un\G24999
CH16 Un\G25000 to Un\G25999
ON
ONON
OFF
OFF
'CH1 Logging enable/disable setting'
(Un\G535)
'Operating condition setting request' (Y9)
'Operating condition setting completed
flag' (X9)
Disable
(1)
Enable (0)
Logging starts.