4 OPERATION CONTROL PROGRAMS
4.5 Binary Operations
135
4
Multiplication: *
Setting data
Usable data
: Usable
Description, data type of result
Processing details
The data specified with (S1) is multiplied by the data specified with (S2).
When (S1) and (S2) differ in data type, the data of the smaller data type is converted into that of the greater type before
operation is performed.
Operation error
An operation error will occur if:
(S1) or (S2) is an indirectly specified device and its device No. is outside the range.
Program example
Program which substitutes the result of multiplying K123 by #0 to W0
Program which substitutes the result of multiplying #0F by #10 to D0L
The 64-bit floating-point type data are used for multiplication, and the result is converted into the 32-bit integer type and then
substituted.
Format Number of basic steps Usable steps
F/FS G
(S1)*(S2) 7 
Setting
data
Usable Data
Bit
device
Word device Constant Calculation
expression
Bit
conditional
expression
Comparison
conditional
expression
16-bit
integer
type
32-bit
integer
type (L)
64-bit
floating
point
type (F)
16-bit
integer
type
(K/H)
32-bit
integer
type
(K/H, L)
64-bit
floating
point
type (K)
(S1) 
(S2) 
Setting data Description Data type of result
(S1) Multiplicand data Data type of (S1) or (S2) which is greater
(S2) Multiplier data
56088W0
456#0
*
123
W0 = K123*#0
D0L
*
1518532
D1 D0
12345.789
#2 #1
123#10
#3 #0
1518532.047
D0L = #0F*#10