3 TROUBLESHOOTING
3.1 Procedure for Troubleshooting
47
3
3 TROUBLESHOOTING
This chapter describes errors that may occur while using the high-speed counter module, and those troubleshooting.
Throughout the chapter, the I/O numbers (X/Y) and buffer memory addresses are described on the basis of
the case of CH1.
To check them of CH2, refer to the following:
Page 54 List of I/O signals
Page 60 List of buffer memory addresses
3.1 Procedure for Troubleshooting
If a trouble occurs, try the following troubleshooting steps:
1. Check whether each module is mounted and wired correctly.
( MELSEC iQ-R Module Configuration Manual)
2. Check the LEDs of the power supply module and CPU module. ( User's Manual of each module)
3. Check the error cause and corrective action by the symptom to correct the error. ( Page 48 Troubleshooting by
Symptom)
3.2 Checking Module Status
An overflow error can be checked in CH1 Overflow detection (Un\G8).
Error information to be detected by the high-speed counter module
Description and cause Where to check the error information Action
Overflow error
In linear counter, an up pulse has been counted
from the present value 2147483647.
In linear counter, a down pulse has been counted
from the present value -2147483648.
Overflow detection flag
CH1 Overflow detection (Un\G8) stores one of the following
values:
0: No overflow
1: Overflow occurred
Execute a preset to clear the overflow
error.