EasyManua.ls Logo

Mitsubishi Electric RD62P2E - Page 76

Mitsubishi Electric RD62P2E
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74
APPENDICES
Appendix 4 Operation Examples of When the Remote Head Module Is Mounted
4. Configure the setting not to use the module labels.
5. Set "Basic setting" of "Module Parameter" of the high-speed counter module as shown below.
[Navigation window] [Parameter] [Module Information] [RD62P2] [Module Parameter] [Basic setting]
*1 Use CH1 only. For CH2, setting items are all default value.
*2 Set the parameter only when the ring counter function is used.
Setting item
*1
Setting value
Pulse input mode 3: 2-phase multiple of 1
Counting speed setting 2: 200kpps
Counter type Set the parameter according to the requirement of users.
Counter operation mode Set the parameter according to the mode used.
Preset Value Setting 2500
Coincidence output point No.1 1000
Ring Counter Upper Limit Value 5000
*2
Ring Counter Lower Limit Value -5000
*2

Table of Contents

Related product manuals