14 TROUBLESHOOTING
14.5 List of Error Codes
607
14
1AB4H Deceleration time 1
setting error
The setting value of the detailed parameter 2
"Deceleration time 1" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AB5H Deceleration time 2
setting error
The setting value of the detailed parameter 2
"Deceleration time 2" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AB6H Deceleration time 3
setting error
The setting value of the detailed parameter 2
"Deceleration time 3" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AB7H JOG speed limit
value error
The setting value of the detailed parameter 2 "[Pr.31]
JOG speed limit value" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
When the PLC READY signal [Y0] is not turned ON
after the setting value is corrected, turn the PLC
READY signal [Y0] from OFF to ON.
1AB8H JOG speed limit
value error
The setting value of the detailed parameter 2 "[Pr.31]
JOG speed limit value" exceeds the "[Pr.8] Speed limit
value".
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
When the PLC READY signal [Y0] is not turned ON
after the setting value is set to equal to or less than the
"[Pr.8] Speed limit value", turn the PLC READY signal
[Y0] from OFF to ON.
1AB9H JOG speed limit
value error
The setting value of the detailed parameter 2 "[Pr.31]
JOG speed limit value" is smaller than the "[Pr.7] Bias
speed at start".
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
When the PLC READY signal [Y0] is not turned ON
after the setting value is set to equal to or more than
the "[Pr.7] Bias speed at start", turn the PLC READY
signal [Y0] from OFF to ON.
1ABAH Manual pulse
generator speed limit
value error
The setting value of the detailed parameter 2 "Manual
pulse generator speed limit value" is outside the setting
range.
[Operation status at error occurrence]
At the power on or when the PLC READY signal [Y0] is
turned from OFF to ON: The READY signal [X0] is not
turned ON.
At start: The system does not operate.
Correct the setting value and turn the PLC READY
signal [Y0] from OFF to ON.
Error code
(Hexadecimal)
Error name Error details and causes Remedy