608
14 TROUBLESHOOTING
14.5 List of Error Codes
1ABBH Manual pulse
generator speed limit
value error
The setting value of the detailed parameter 2 "Manual
pulse generator speed limit value" exceeds the "speed
limit value".
[Operation status at error occurrence]
At the power on or when the power supply is turned
from OFF to ON, or the PLC READY signal [Y0] is
turned from OFF to ON: The READY signal [X0] is not
turned ON.
At start: The system does not operate.
Set a value equal to or less than the speed limit value.
1ABCH JOG acceleration
time selection setting
error
The setting value of the detailed parameter 2 "JOG
operation acceleration time selection" is outside the
setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1ABDH JOG deceleration
time selection setting
error
The setting value of the detailed parameter 2 "JOG
operation deceleration time selection" is outside the
setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1ABEH Acceleration/
deceleration process
selection setting
error
The setting value of the detailed parameter 2
"Acceleration/deceleration process selection" is outside
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1ABFH S-curve ratio setting
error
The setting value of the detailed parameter 2 "S-curve
ratio" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AC0H Illegal sudden stop
deceleration time
The setting value of the detailed parameter 2 "Sudden
stop deceleration time" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
Error code
(Hexadecimal)
Error name Error details and causes Remedy