APPENDICES APPENDIX
Appendix 3 Compatible Devices with SSCNETIII(/H)
629
A
Reset selection/disconnected PU detection/PU stop selection
When PU stop is executed in FR-A700 series, position error excessive, etc. occur because a command from Simple Motion
module does not stop. Set "0 to 3" in the parameter of the inverter "[Pr.75] Reset selection/ disconnected PU detection/PU
stop selection". To stop FR-A700 series, use the stop signal and the forced stop of Simple Motion module, or use the output
stop (MRS) of FR-A700 series.
*1 Note that the default value is set to "14". (Change the value to "0 to 3".)
In-position range
Set the servo parameter "In-position range (PA10)" and the parameter of the inverter "[Pr.426] In-position width" to be
matched. Otherwise, it may not operate correctly.
n: Axis No. - 1
Setting item Default
value
Setting
value
Details
[Pr.75] Reset selection/disconnected PU detection/
PU stop selection
14
*1
0 Reset input is always enabled.
If the PU is disconnected, operation will be continued.
PU stop is disabled at SSCNET connection.
1 A reset can be input only when the protective function is activated.
If the PU is disconnected, operation will be continued.
PU stop is disabled at SSCNET connection.
2 Reset input is always enabled.
When the PU is disconnected, the inverter trips.
PU stop is disabled at SSCNET connection.
3 A reset can be input only when the protective function is activated.
When the PU is disconnected, the inverter trips.
PU stop is disabled at SSCNET connection.
14 Reset input is always enabled.
If the PU is disconnected, operation will be continued.
Deceleration stop by PU stop in any operation mode.
15 A reset can be input only when the protective function is activated.
If the PU is disconnected, operation will be continued.
Deceleration stop by PU stop in any operation mode.
16 Reset input is always enabled.
When the PU is disconnected, the inverter trips.
Deceleration stop by PU stop in any operation mode.
17 A reset can be input only when the protective function is activated.
When the PU is disconnected, the inverter trips.
Deceleration stop by PU stop in any operation mode.
Setting item Default value Setting range Buffer memory address
PA10 In-position range 100 (pulse) 0 to 65535 (pulse) 28410+100n
Setting item Default value Setting range Details
[Pr.426] In-position width 100 (pulse) 0 to 32767 (pulse) When droop pulses have fallen below the setting value, the in-position
signal turns ON.