119
-
'18 • SCM-T-251
Indoor unit
combination
Cooling capacity (kW) Power consumption (W) Standard current (A)
Indoor unit capacity (kW) Total capacity (kW)
Min.
Standard
Max. 220V 230V 240V
A B C Min.
Standard
max.
1
unit
2
units
3
units
Indoor unit
combination
Heating capacity (kW) Power consumption (W) Standard current (A)
Indoor unit capacity (kW) Total capacity (kW)
Min.
Standard
Max. 220V 230V 240V
A B C Min.
Standard
max.
1
unit
2
units
<Cooling>
<Heating>
20 3.0 - - 1.4 3.0 3.7 480 820 1100 3.9 3.7 3.6
25 3.4 - - 1.4 3.4 4.2 480 980 1240 4.6 4.4 4.2
35 4.5 - - 1.4 4.5 5.0 480 1270 1490 6.0 5.7 5.5
50 5.8 - - 1.4 5.8 6.2 480 1710 2260 7.9 7.6 7.3
20 + 20 2.95 2.95 - 2.0 5.9 7.3 540 1450 2580 6.7 6.4 6.2
20 + 25 2.67
3.33 - 2.0 6.0 7.3 540 1500 2580 7.0 6.7 6.4
20 + 35 2.29 4.01 - 2.0 6.3 7.3 540 1580 2580 7.3 7.0 6.7
20 + 50 1.89 4.71 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
25 + 25 3.05 3.05 - 2.0 6.1 7.3 540 1530 2580 7.1 6.8 6.5
25 + 35 2.67 3.73 - 2.0 6.4 7.3 540 1610 2580 7.5 7.1 6.8
25 + 50 2.20 4.40 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
35 + 35 3.30 3.30 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
35 + 50 2.72 3.88 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
20 2.0 - - 1.8 2.0 2.8 500 550 900 2.6 2.5 2.4
25 2.5 - - 1.8 2.5 3.4 500 720 1070 3.4 3.2 3.1
35 3.5 - - 1.8 3.5 3.9 500 1080 1230 5.1 4.8 4.6
50 5.0 - - 1.8 5.0 5.5 500 1700 2000 7.9 7.5 7.2
20 + 20 2.00 2.00 - 3.0 4.0 5.7 570 910 1800 4.2 4.1 3.9
20 + 25 1.91 2.39 - 3.0 4.3 5.9 570 1070 1980 5.0 4.8 4.6
20 + 35 1.82 3.18 - 3.0 5.0 6.2 570 1430 2070 6.6 6.3 6.1
20 + 50 1.71 4.29 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
25 + 25 2.35 2.35 - 3.0 4.7 6.2 570 1270 2070 5.9 5.6 5.4
25 + 35 2.21 3.09 - 3.0 5.3 6.5 570 1600 2150 7.4 7.1 6.8
25 + 50 2.00 4.00 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
35 + 35 3.00 3.00 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
35 + 50 2.47 3.53 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
20 + 20 + 20 1.67 1.67 1.67 3.4 5.0 7.1 690 1050 2150 4.9 4.7 4.5
20 + 20 + 25 1.60 1.60 2.00 3.4 5.2 7.1 690 1160 2150 5.4 5.1 4.9
20 + 20 + 35 1.49 1.49 2.61 3.4 5.6 7.1 690 1330 2150 6.2 5.9 5.7
20 + 25 + 25 1.54 1.93 1.93 3.4 5.4 7.1 690 1260 2150 5.8 5.6 5.4
20 + 25 + 35 1.45 1.81 2.54 3.4 5.8 7.1 690 1430 2150 6.6 6.3 6.1
25 + 25 + 25 1.87 1.87 1.87 3.4 5.6 7.1 690 1330 2150 6.2 5.9 5.7
25 + 25 + 35 1.76 1.76 2.47 3.4 6.0 7.1 690 1490 2150 6.9 6.6 6.3
5. TABLE OF INDOOR UNIT COMBINATIONS
The combinations of the indoor units is indicated by numbers. They are read as follows.
(Example) SRK20ZSX-S20 SRK25ZSX-S25
The capacity of the indoor units is shown by rooms. If this exceeds the maximum capacity of the outdoor unit, the demand
capacity will be proportionally distributed.
If units are to be combined, use the table below to make the proper selection.
Number of connectable indoor units
SCM50ZS-S1,60ZM-S1
2
3
MIN
MAX
Note(1) In case of combination with SRK-ZMX-S, SRK71ZR-S, FDEN50VF only, 3 Indoor units can be connectable.
In case of SRK71ZR-SSRK71ZR-S, 2 Indoor units can be connectable.
(1) Model SCM50ZS-S1
(a) Indoor unit SRK ZSX type only