119
-
'18 • SCM-T-251
Indoor unit
combination
Cooling capacity (kW) Power consumption (W) Standard current (A)
Indoor unit capacity (kW) Total capacity (kW)
Min.
Standard
Max. 220V 230V 240V
A B C Min.
Standard
max.
1
unit
2
units
3
units
Indoor unit
combination
Heating capacity (kW) Power consumption (W) Standard current (A)
Indoor unit capacity (kW) Total capacity (kW)
Min.
Standard
Max. 220V 230V 240V
A B C Min.
Standard
max.
1
unit
2
units
<Cooling>
<Heating>
20 3.0 - - 1.4 3.0 3.7 480 820 1100 3.9 3.7 3.6
25 3.4 - - 1.4 3.4 4.2 480 980 1240 4.6 4.4 4.2
35 4.5 - - 1.4 4.5 5.0 480 1270 1490 6.0 5.7 5.5
50 5.8 - - 1.4 5.8 6.2 480 1710 2260 7.9 7.6 7.3
20 + 20 2.95 2.95 - 2.0 5.9 7.3 540 1450 2580 6.7 6.4 6.2
20 + 25 2.67
3.33 - 2.0 6.0 7.3 540 1500 2580 7.0 6.7 6.4
20 + 35 2.29 4.01 - 2.0 6.3 7.3 540 1580 2580 7.3 7.0 6.7
20 + 50 1.89 4.71 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
25 + 25 3.05 3.05 - 2.0 6.1 7.3 540 1530 2580 7.1 6.8 6.5
25 + 35 2.67 3.73 - 2.0 6.4 7.3 540 1610 2580 7.5 7.1 6.8
25 + 50 2.20 4.40 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
35 + 35 3.30 3.30 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
35 + 50 2.72 3.88 - 2.0 6.6 7.3 540 1670 2580 7.7 7.4 7.1
20 2.0 - - 1.8 2.0 2.8 500 550 900 2.6 2.5 2.4
25 2.5 - - 1.8 2.5 3.4 500 720 1070 3.4 3.2 3.1
35 3.5 - - 1.8 3.5 3.9 500 1080 1230 5.1 4.8 4.6
50 5.0 - - 1.8 5.0 5.5 500 1700 2000 7.9 7.5 7.2
20 + 20 2.00 2.00 - 3.0 4.0 5.7 570 910 1800 4.2 4.1 3.9
20 + 25 1.91 2.39 - 3.0 4.3 5.9 570 1070 1980 5.0 4.8 4.6
20 + 35 1.82 3.18 - 3.0 5.0 6.2 570 1430 2070 6.6 6.3 6.1
20 + 50 1.71 4.29 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
25 + 25 2.35 2.35 - 3.0 4.7 6.2 570 1270 2070 5.9 5.6 5.4
25 + 35 2.21 3.09 - 3.0 5.3 6.5 570 1600 2150 7.4 7.1 6.8
25 + 50 2.00 4.00 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
35 + 35 3.00 3.00 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
35 + 50 2.47 3.53 - 3.0 6.0 6.5 570 1960 2150 9.0 8.6 8.2
20 + 20 + 20 1.67 1.67 1.67 3.4 5.0 7.1 690 1050 2150 4.9 4.7 4.5
20 + 20 + 25 1.60 1.60 2.00 3.4 5.2 7.1 690 1160 2150 5.4 5.1 4.9
20 + 20 + 35 1.49 1.49 2.61 3.4 5.6 7.1 690 1330 2150 6.2 5.9 5.7
20 + 25 + 25 1.54 1.93 1.93 3.4 5.4 7.1 690 1260 2150 5.8 5.6 5.4
20 + 25 + 35 1.45 1.81 2.54 3.4 5.8 7.1 690 1430 2150 6.6 6.3 6.1
25 + 25 + 25 1.87 1.87 1.87 3.4 5.6 7.1 690 1330 2150 6.2 5.9 5.7
25 + 25 + 35 1.76 1.76 2.47 3.4 6.0 7.1 690 1490 2150 6.9 6.6 6.3
5. TABLE OF INDOOR UNIT COMBINATIONS
●
The combinations of the indoor units is indicated by numbers. They are read as follows.
(Example) SRK20ZSX-S→20 SRK25ZSX-S→25
●
The capacity of the indoor units is shown by rooms. If this exceeds the maximum capacity of the outdoor unit, the demand
capacity will be proportionally distributed.
●
If units are to be combined, use the table below to make the proper selection.
・Number of connectable indoor units
SCM50ZS-S1,60ZM-S1
2
3
MIN
MAX
Note(1) In case of combination with SRK-ZMX-S, SRK71ZR-S, FDEN50VF only, 3 Indoor units can be connectable.
In case of SRK71ZR-S+SRK71ZR-S, 2 Indoor units can be connectable.
(1) Model SCM50ZS-S1
(a) Indoor unit SRK ZSX type only
5. TABLE OF INDOOR UNIT COMBINATIONS