(9) Inching prevention
When the compressor becomes to the thermostat operation within 5 minutes since operation start or becomes dehumidify-
ing operation, the operation is continued with the compressor speed of minimum rps forcibly.
(8) Crankcase heater
(a) Operating conditions
This control starts
whenalltheconditionsbelowaresatised.
(i) After the operation mode is changed to stop and the compressor speed becomes 0 rps continuously for 30 minutes.
(ii) When the temperature detected by the outdoor air temperature (Tho-A) is -2°C or lower after the compressor stops.
(7) Refrigeration cycle system protective control
(a) Starting condition
Thiscontrolstartswhenthefollowingconditionsaresatised.
(i)
 
When it has elapsed 30 minutes after the compressor was changed from OFF to ON in the cooling operation mode
for more than 5 minutes.
(ii)
 
Whenthecompressorspeedhassatisedthefollowingconditions.
(iii)
 
When the indoor air temperature of running indoor unit (Th1) and the indoor heat exchanger temperature (Th2) have
satisedthefollowingconditionevenononeunit.
(b) Contents of control
(i) Stop the compressor and delay the start, and then restarts.
(ii) Compressor stops by the abnormal stop when the compressor stop has occurred 3 times in one hour.
Unit
Compressor speed
Indoor air temperature
(Th1, °C)
Indoor air temperature (Th1) and indoor
heat exchanger temperature (Th2)
Duration
SCM50 SCM60
1
60 rps 40 rps
10
<
=
Th1
<
=
40
Th1 - 4 < Th2
5 minute
2
70 rps 50 rps
3
80 rps 60 rps Th1 - 3 < Th2
(b) Detail of operation
The crankcase heater operates, warming up the compressor, then refrigerant begins circulating smoothly when the
air-conditioner starts its heating operation, and heating begins.
(c) Reset conditions
When the temperature detected by the outdoor air temperature (Tho-A) reaches 0°C or higher, or the operation mode
changes from stop to cooling or heating.
-
189
-