106
-
'10 • SCM-SM-094
Stays OFF
Keeps flashing
Error code
Remote controller:
LED Green Red
Indoor
Content
E42
Current cut (2/2)
Outdoor
1
time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
After
resetting power for
several times does it
become normal?
NO
YES
Temporary noise may cause of anomaly.
If noise source can be found, take countermeasure.
Is the
checked result of power
transistor module
OK?
NO
Is the space for installation of indoor and/or outdoor unit enough?
Is there any short circuit of air on indoor and/or outdoor unit?
At cooling, does the outdoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
Is there any liquid flooding?
Is the superheat within normal range?
Is the low pressure sensor and suction pipe temperature
thermistor normal?
Is there any anoumalous sound on the compressor?
YES
Continue from previous page
YES
Defective outdoor main
PCB
ª
Replace.
Defective outdoor main
PCB
ª
Replace.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3.
Condition of Error displayed
If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
4. Presumable cause
Defective outdoor main PCB
Faulty power supply
Insufficient refrigerant amount
Faulty compressor
Faulty power transistor
module
Note:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM80ZJ-S and is the answer not in the manual?

Mitsubishi Heavy Industries SCM80ZJ-S Specifications

General IconGeneral
Cooling Capacity8.0 kW
Heating Capacity9.0 kW
Power Supply220-240 V, 50 Hz
Sound Pressure Level (Cooling)Varies depending on the connected indoor units
Sound Pressure Level (Heating)49 dB

Related product manuals