2 Access door
Access door must be provided without fail.
Dimensions of access door and service space
( See exterior dimensions in page 11 )
1 Supply air duct
3-spot with
200 type duct are the standard specifications. Determine the number of spots based on following table.
Use a band, etc. to connect the indoor unit and the supply air duct flange.
Conduct the duct installation work before finshing the ceiling.
FDUMA302R
2 ~ 3-spot
(1)
Bad exampleBad example Good example
Notes (1) Shield the central supply air port for 2-spot.
Limit the difference in length between spots at less than 2:1.
Reduce the length of duct as much as possible.
Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)
3 Return air port
¡ When shipped, the return air port lies on the back.
¡ When connecting the duct to the return air port, remove the air filte if it is fitted to return air port.
¡ When placing the return air port to carry out suction from the bottom side, use the following procedure to replace the
return air duct joint and the bottom plate.
¡ Make sure to insulate the duct to prevent dewing on it.
4 Install the specitic supply air duct in a location where the air will circulate to the entire room.
¡ The duct connection is specific to the 200 circular duct.
¡ Conduct the installation of the specific supply air hole and the connection of
the duct before attaching them to the ceiling.
¡ Insulate the area where the duct is secured by a band for dew condensation
prevention.
Remove the screws which fasten
the bottom plate and the duct joint
on the return air port of the unit.
Replace the removed bottom plate
and duct joint.
Fit the duct joint with a screw,
fit the bottom plate.
Secure with a band,etc.
Supply air
duct