47
-
'20 • PAC-SM-351
(
f
) Over-current protection current safe controls I, II
Detecting the outdoor inverter input (primary) current and the output (secondary) current, if the current values exceed
setting values, the compressor speed (frequency) is controlled to protect the inverter.
Retention
Reduces frequency
at each minute.
Reset
BA
Current (A)
12
14
16
18
20
22
24
5040 60 70 80 90 100 110 120 130
Control or reset v
alve (A)
Compressor speed (frequency) (rps)
(Fig. C) The control value “A” and the reset value vary depending
on the compressor speed.
Reset valve B
Control valve A
(
g
) Power transistor temperature protection
(i) Protective control
If the power transistor temperature (detected with TIP) exceeds the setting value, the compressor speed (frequency)
is controlled to suppress the rise of power transistor temperature.
Retention
Reduces compressor frequency
at each minute.
Reset
76(70) 80(73)
Power transistor temperature (°C)
Note (1) Value in ( ) are for the single phase model.
(
h
) Anomalous power transistor current
(i)
Prevents over-current on the inverter. If the current value in the power transistor exceeds the setting value, the
compressor stops.
(ii) Ifthecurrentvalueinthepowertransistorexceedsthespeciedvalueandthecompressorstops4timeswithin30
minutes, E42 is displayed on the remote control and it enters the anomalous stop mode.
(
i
) Anomalous inverter PCB
If the power transistor detects any anomaly for 15 minutes, including the stop of compressor, E51 is displayed on the
remote control and it enters the anomalous stop mode.
(
j
) Anti-frost control by the compressor frequency control
(i) If the indoor heat exchanger temperature (detected with Thi-R) exceeds the setting value at 4 minutes after the
start of compressor, the compressor speed (frequency) is controlled to initiate the anti-frost control of indoor heat
exchanger.
(ii) When there are 3 indoor heat exchanger temperatures (Thi-R), the lowest temperature is detected.
1.5 3.5
Retention
Reduces compressor frequency
at each minute.
Reset
Indoor heat exchan
g
er temperature (°C)
(iii) Regarding the anti-frost control by the operation stop, refer to the operation control function by the indoor control
and the cooling, dehumidifying frost prevention of page 21.
Model
Cooling Heating
Control
value A
Reset
value B
Control
value A
Reset
value B
Primary
current
side
FDC100
11.0 (23.0) 10.0 (22.0) 11.0 (23.0) 10.0 (22.0)
FDC125, 140
11.0 (23.0) 10.0 (22.0) 11.0 (25.0) 10.0 (24.0)
Secandary
current
side
FDC100
11.5 (Fig.C)
10.5 (Fig.C-1)
11.5 (Fig.C)
10.5 (Fig.C-1)
FDC125, 140
11.5 (Fig.C)
10.5 (Fig.C-1)
11.5 (Fig.C)
10.5 (Fig.C-1)
Note (1) Value in ( ) are for the single phase models.