158
Set V/F pattern
(2) Adjustment of elevator mode (Pr. 61, Pr. 64)
By setting the adjustment parameters Pr. 61 and Pr. 64, the application range can be made wider.
Parameter
Number
Name Setting Range Description
61
Reference
current
01800 or
less
0 to 500A
For example, when the motor and inverter are different in
capacity, set the rated motor current value. Set reference
current (A) of the stall prevention operation level
02160 or
more
0 to 3600A
9999 (initial value) The rated inverter output current is defined as reference.
64
Starting
frequency for
elevator mode
0 to 10Hz Set the starting frequency for the elevator mode.
9999 (initial value) Starting frequency 2Hz
REMARKS
Even if elevator mode has been selected, inputting the jog signal (jog operation), RT signal (second function selection) or X9
signal (third function selection) during an inverter stop will switch to the normal operation and give priority to jog operation or
second and third function selection. Note that JOG and RT signal input is invalid even if JOG signal and RT signal are input
during operation with acceleration/deceleration selected.
Elevator mode is invalid when advanced magnetic flux vector, real sensorless vector control or vector control is selected.
Since the Pr. 61 and Pr. 64 settings automatically return to the initial value (9999) if the Pr. 292 setting is changed, set Pr. 292 first
when you need to set Pr. 61 and Pr. 64.
Parameters referred to
Pr. 570 Multiple rating setting Refer to page 149