49
(
3
)
Combined operation mode 1 (Pr. 79 "operation mode selection" = 3)
The start signal is an external signal.
The frequency setting signal is set using the optional control
panel or parameter unit.
Preparation
!
Start signal ...............Switch, relay, etc.
!
Operation unit...........Control panel (FR-PA02
-02
) or
parameter unit (FR-PU04)
!
Connection cable......Refer to (1) PU operation mode.
!
FR-E5P (option) .......Refer to (1) PU operation mode.
(
4
)
Combined operation mode 2 (Pr. 79 "operation mode selection" = 4)
The start signal is entered from the operation command key
of the optional control panel.
The frequency setting signal is set using the external
frequency setting signal.
Preparation
!
Frequency ..................0 to 5V, 0 to 10V or 4 to 20mA DC
setting signal signals from an external
potentiometer or from outside the
inverter
!
Operation unit.............Control panel (FR-PA02
-02
) or
parameter unit (FR-PU04)
!
Connection cable........Refer to (1) PU operation mode.
!
FR-E5P (option) .........Refer to (1) PU operation mode.
(
5
)
Communication operation mode
(Pr. 79 "operation mode selection" = 0 or 1)
Communication operation can be performed by connecting a personal computer and
the PU connector with the RS-485 communication cable.
The inverter setup software is available as an FR-E500 inverter start-up support
software package.
Preparation
!
Connection cable..........................Connector: RJ45 connector
Cable: Cable conforming to EIA568
(e.g. 10BASE-T cable)
!
Personal computer
!
RS-485, RS-232C converter.........
To be prepared when the communication port of the
personal computer has RS-232C specifications.
3