Common specifications
120
SPECIFICATIONS
 This protective function is not available in the initial status.
 Temperature applicable for a short time, e.g. in transit.
 2.9 m/s
2
or less for the FR-F846-01800(75K) or higher.
Environment
Surrounding air
temperature
-10°C to +40°C (non-freezing)
Surrounding air humidity
With circuit board coating (conforming to IEC60721-3-3:1994 3C2/3S2): 95% RH or less (non-condensing)
Without circuit board coating: 90% RH or less (non-condensing)
Storage temperature
-20°C to +65°C
Atmosphere
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)
Altitude/vibration
Maximum 2500 m (for the installation at an altitude above 1,000 m, derate the rated current 3% per 500 m.), 5.9 m/s
2
or
less at 10 to 55 Hz (directions of X, Y, Z axes)