Operation panel (FR-LU08-01)
INSTALLATION AND WIRING
51
2
2.7.2 Outline of the Main monitor indicator
Symbol Name Description
a Main monitor item/data
Displays the output frequency, output current, output voltage, faults history, and others.
The Main monitor screen can be changed by the following methods.
Shifting the Main monitor screen using or
Changing the main monitor item using the Function menu
Changing the main monitor item using Pr.52 Operation panel main monitor selection
(For the details, refer to the Instruction Manual of the FR-LU08(-01).)
b Rotation direction
Displays the direction of the start command ([STF]: forward, [STR]: reverse).
([---] shows that no start command is input, or that both forward and reverse directions are ON.)
c Operating status
Displays the operating status of the inverter.
[STOP]: During stop
[FWD]: During forward rotation
[REV]: During reverse rotation
[JOGf]: During JOG forward rotation
[JOGr]: During JOG reverse rotation
[ALARM]: At fault occurrence
dClock
Displays time. With a battery installed, the clock keeps working even if the inverter power is turned
OFF. (For the details, refer to the Instruction Manual of the FR-LU08(-01).)
e Tuning status
Displays the offline auto tuning status of the inverter.
[TUNE]: During turning or tuning completed
[TUNE] highlighted and flickering: Tuning error
f
USB connection/
password locked
Displays the connection status of the USB A connector of the inverter and password function setting
status.
[USB-A]: USB connection recognized
[USB-A] highlighted: USB ready
[USB-A] flickering: During USB operation
[LOCK]: Password locked
g
PLC function/JOG
operation
Displays the status of the PLC function and JOG operation.
[P.RUN]: During stop with the PLC function enabled
[P.RUN] highlighted: During PLC function operation
[P.RUN] highlighted and flickering: Operation error in the PLC function
[JOG]: JOG operation enabled
h Warning Displays an inverter warning.
i Unit Shows the unit of the value on the main monitor.
j Operation mode
Displays the operation mode.
[AUTO]: AUTO (External) operation mode
[HAND]: HAND (PU) operation mode
[EXTj]: AUTOJOG (External JOG) operation mode
[PUj]: HANDJOG (PUJOG) operation mode
[NET]: Network operation mode
[PU+E]: AUTO (External) / HAND (PU) combined operation mode
k Software key Displays operations performed by pressing the F1 (left), F2 (center), or F3 (right) keys.
lScroll
Displayed when any data can be scrolled by turning .
PREV
SET
NEXT
STF
STOP
HAND
Hz
0. 00
Output frequency
TUNE USB- A P. RUN
12: 34
OL
(a)
(b)
(c)
(e)
(f)
(d)
(h)
(g)
(i)
(j)
(k)
(k)
(l)
(PREV)
(NEXT)

Table of Contents