EasyManua.ls Logo

Mitsubishi FREQROL-SF - Alarm No.26 (PL) Power Phase Lack; Alarm No.27 (CPUE) CPU Error (Division error)

Mitsubishi FREQROL-SF
219 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(4) Alarm
No.l7(BE)
P.C.B
error
[Whether a component (especially
A/D converter) on the printed cir-
cuit board is normal or abnormal
is checked.
1
Item
Cause Check Remedy
A component (especially,
D
Replace the SF-CA card with
o
Replace the SF-CA card with
1
A/D
converter) on the
the new one and check that
the new one.
printed circuit board
the equipment correctly
(See Section 2.4.4.)
SF-CA card is defective. works.
The power of the
equip-
D
Check that the NF is turned
o
Turn on the NF.
ment is turned on while
off.
the NF in the unit is
o
To check only the control
turned off.
circuit without appearance
of alarm No.17, set the
2
parameter X58 CVHS to
"1".
However,
to return back to
the normal operation mode,
make sure to set the
158
CVHS to
"0".
Otherwise,
the
LED1
(which lights dur-
ing regeneration) on the
SF-CA card continuously
lights.
(5) Alarm
No.20(NSl)
IC MAC007 Error
[The internal codes of the IC MAC007
on the SF-CA card are checked.]
Item
Cause Check
Remedy
The IC (MAC
007)
on the
D
Replace the SF-CA card with a
o
Replace the printed circuit
1
printed circuit board
new one and check that the board SF-CA card with the
SF-CA card does not
equipment correctly works. new one.
correctly work.
(See Section
2.4.4.)
-
25
-

Table of Contents