No.
11 When PZ-60DR-E is used, the
timer operation does not work.
Timer operation does not work in the following circumstances:
• When the timer function is set to OFF.
• During the day of the week and time setting / During function selection /
During timer setting
• When “CENTRAL” is displayed.
—
Error Cause
Reference
12 When PZ-41SLB-E is used,
the operation will not be in
accordance with the setting of
the function selection switch
on the Lossnay circuit board.
The settings will be disabled for switches (SW2-6, SW5-1, SW5-4, SW5-5,
SW5-7, and SW5-8).
Page
38
13 When PZ-60DR-E is used,
“ (“Locked” indica-
tor)” is displayed, and the
remote controller cannot be
operated.
In the following circumstances “ (“Locked” indicator)” is displayed,
and the applicable function button cannot be operated.
• The operation lock is enabled. (Buttons other than the “ON/OFF” button,
or all buttons)
• When operating with the High / Low / Extra Low fan speed switching input
(“Fan Speed Adjustment” button, and “Extra Low fan speed” button)
• When operating with the bypass ventilation switching input. (“Function
selector” button)
• During the night purge operation. (“Function selector” button)
• When two remote controllers are used, one of the remote controllers is
set to the function selection mode or the maintenance mode. (All buttons)
Page
40
33, 34
35
36, 37
40- 43
15 The Lossnay unit starts by
itself at night.
When the night purge setting is set to “on”, the night purge operation will be
performed at nighttime.
Page
36, 37
16 Night purge operation does
not work even though Night
purge operation is set.
The night purge operation will not be performed in the following circum-
stances:
• The night purge conditions have not been satisfied.
• Lossnay has been started or stopped during the display of “ (Night
purge)”.
• Night purge operation will not be performed when “CENTRAL” is dis-
played.
Page
36, 37
17 Damper board does not oper-
ate.
When switching the ventilation mode with the remote controller, a maxi-
mum delay of 30 seconds will be generated depending on the timing.
Page
29
18 Delay operation does not work
even though Delay operation
is set.
• Delay operation will not start until 2 hours after the Lossnay stopped.
• When the pulse input setting is set to “on”, delay operation will not start.
• When using PZ-60DR-E and PZ-41SLB-E, operation will be according to
the setting of the remote controller.
Page
32
19 Operation monitor output will
not be output until several
seconds after the fan started
operation.
When the TM4
9, 0 output setting is set to operation monitor with delay
function 1 (SW2-8 is ON), the operation monitor will be output 10 seconds
after the fan started operation.
Page
33
20 After operation has been
stopped with the remote con-
troller, the fan continues to run
for a while.
When the TM4 9, 0 output setting is set to operation monitor with delay
function 1 (SW2-8 is ON), or when the TM3 6, 7 output setting is set to
operation monitor with delay function 2 (SW5-6 is ON), the fan will stop 3
minutes after stop with the remote controller.
Page
27
—
64
—
14 The supply air fan periodically
stops operating.
• When the outdoor temperature is -10°C or lower, the fan is periodically
stopped for approximately 10 minutes to prevent freezing of the Lossnay
core. (Cold region specifications)
•
When the Lossnay unit has duct connections and interlocked with Mr. Slim
or City Multi indoor units, the fan will stop during air conditioner defrosting.
Page
27