12-55
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
3301
[SP. PARA ERROR]
• The refresh setting of the intelligent function
module exceeded the file register capacity.
• The intelligent function module set in GX
Configurator differs from the actually mounted
module.
â– Collateral information
• Common information: File name
• Individual information: Parameter number
*4
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
• Change the file register file for the one which
allows refresh in the whole range.
• Check the parameter setting.
• Check the auto refresh setting.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Q00J/Q00/Q01
Qn(H)
*8
QnPH
QnPRH
QnU
LCPU
[SP. PARA ERROR]
The intelligent function module's refresh parameter
setting is outside the available range.
â– Collateral information
• Common information: File name
• Individual information: Parameter number
*4
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
• Check the parameter setting.
• Check the auto refresh setting.
QCPU
LCPU
[SP. PARA ERROR]
The setting of the refresh parameter range crosses
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
â– Collateral information
• Common information: File name
• Individual information: Parameter number
*4
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
Set the refresh parameter range so that it does
not cross over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
QnU
LCPU
3302
[SP. PARA ERROR]
The intelligent function module's refresh parameter
are abnormal.
â– Collateral information
• Common information: File name
• Individual information: Parameter number
*4
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
Check the parameter setting.
QCPU
LCPU
3303
[SP. PARA ERROR]
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to the
intelligent function module under control of another
station.
â– Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
â– Diagnostic Timing
• At power-on/At reset/STOP→RUN/At writing to
programmable controller
• Delete the automatic refresh setting or other
parameter setting of the intelligent function
module under control of another CPU.
• Change the setting to the automatic refresh
setting or other parameter setting of the
intelligent function module under control of the
host CPU.
Q00/Q01
*8
Qn(H)
*8
QnPH
QnU
*18
Error
Code
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU