MELSEC-Q/QnA
6 BASIC INSTRUCTIONS
(4) The following will happen when an underflow or overflow is generated in an operation result:
The carry flag in this case does not go ON.
K32767 +K2
(H7FFF)
K-32768 +K-2
(H8000)
(H0002)
(HFFFE)
K-32767......A negative value is generated if b15 is 1.
K32766.......A positive value is generated if b15 is 0.
(H7FFE)
(H8001)
-
(1) Subtracts 16-bit BIN data designated by
D
from 16-bit BIN data designated by
S
and stores
the result of the subtraction at the device designated by
D
.
5678 (BIN)
b15- - - - - - - - -b0
4444 (BIN)1234 (BIN)
D S D
b15- - - - - - - - -b0 b15- - - - - - - - -b0
-
(2) Values for
S
and
D
can be designated between -32768 and 32767 (BIN, 16 bits).
(3) The judgment of whether data is positive or negative is made by the most significant bit (b15).
• 0 ....... Positive
• 1 ....... Negative
(4) The following will happen when an underflow or overflow is generated in an operation result:
The carry flag in this case does not go ON.
K32767
-K2
(
H7FFF
)
-K-2
(H8000) (H0002)
K-32767......A negative value is generated if b15 is 1.
K32766.......A positive value is generated if b15 is 0.
(H7FFE)
(
H8001
)
(
H0002
)
K-32768
[Operation Errors]
(1) There are no operation errors associated with the +(P) or -(P) instructions.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC QCPU and is the answer not in the manual?

Mitsubishi MELSEC QCPU Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC QCPU
CategoryController
LanguageEnglish

Related product manuals