18
Type
Frame (A) 100
NF100-CP T/A
Low-inst
Standard
Mag-Only
Generator
690V
500V
440V
400V
230V
AC Breaking
capacity (kA rms)
IEC60947-2
Icu/Ics
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Rated insulation voltage Ui (V) AC
Rated current In (A)
15 ~ 20 225 ± 45
20 ~ 25 300 ± 60
25 ~ 40 375 ± 75
40 ~ 63 600 ± 120
63 ~ 80 945 ± 189
80 ~ 100 1200 ± 240
50
NF50-HRP
Thermal, magnetic
Fixed ampere rating and
instantaneous
15 225 ± 45
20 300 ± 60
30 450 ± 90
40 600 ± 120
50 750 ± 150
23
Magnetic
Fixed ampere rating and
instantaneous
100
NF100-SP T/A
Thermal, magnetic
Adjustable ampere rating
and fixed instantaneous
600
7.5/4
10/5
10/5
25/13
23
15 ~ 20, 20 ~ 25, 25 ~ 40
40 ~ 63, 63 ~ 80, 80 ~ 100
15, 20, 30, 40, 50
15 ~ 20, 20 ~ 25, 25 ~ 40
40 ~ 63, 63 ~ 80, 80 ~ 100
690
2.5/1
20/10
30/15
30/15
85/43
23
690
15/8
25/13
30/15
50/25
234
Thermal, magnetic
Adjustable ampere rating
and fixed instantaneous
15 ~ 20 225 ± 45
20 ~ 25 300 ± 60
25 ~ 40 375 ± 75
40 ~ 63 600 ± 120
63 ~ 80 945 ± 189
80 ~ 100 1200 ± 240
15 150 ± 30
20 200 ± 40
30 300 ± 60
40 400 ± 80
50 500 ± 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi NF50-CP and is the answer not in the manual?

Mitsubishi NF50-CP Specifications

General IconGeneral
BrandMitsubishi
ModelNF50-CP
CategoryCircuit breakers
LanguageEnglish