5 - 17 5 - 17
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-AD)
(2) Command buttons
Make text file
Creates a file containing the screen data in text file format.
End setup
Saves the set data and ends the operation.
Cancel
Cancels the setting and ends the operation.
POINT
The auto refresh settings are stored in an intelligent function module parameter file.
To enable the auto refresh settings after they are written to the CPU module,
perform the operation (1) or (2).
(1) Operate the RUN/STOP switch of the CPU module as follows: STOP
RUN
STOP
RUN.
(2) Set the RUN/STOP switch to RUN, and then turn off and on the power supply or
perform reset of the CPU module.
The auto refresh settings cannot be changed from sequence programs. However,
processing equivalent to auto refresh can be added using the FROM/TO instruction
in the sequence program.