Remove foreign material.
Replace the fan motor.
Check power voltage.
Replace faulty fan motor
and power PCB.
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor control PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
indoor fan motor
3.
Condition of Error displayed
When the actual fan rotation
speed does not reach to the
speed of [required speed-50rpm]
after 2 minutes have been
elapsed since the fan motor
rotation speed command
was output, the unit stops by
detecting indoor fan motor
anomaly.
4. Presumable cause
• Defective indoor power (control)
PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on control PCB
• Blown fuse
• External noise, surge
Note: