If excessive noise/vibration
persists when sufcient
time has elapsed after
stopping the unit, it is
considered that the air-
conditioner is not the
source.
Check the installed
condition carefully, and
correct the position or
insert rubber cushions
or others into the gap, if
necessary.
Prevent the vibration from
transmitting to wall and etc
by xing pipes on the wall
or wrapping rubber cushion
around the pipe which
goes through the hole in
the wall or applying other
appropriate means.
Strength of ceiling
wall, oor, etc. may be
insufcient. Review the
installing position or
reinforce it.
Check for leaning of
installed unit or anomalous
mounting of fan, louver
or motor and specify the
contacting point and correct
it.
When the heat exchanger
or lter is clogged, clean
them. In case that the
unit is installed at the site
where background noise
is very low, small noise
from indoor unit can be
heard, but it is normal.
Before installation, check
for background noise. If
backgound nois is very
low, convince client prior
to installation.
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
➀ Improper installation work
• Improper anti-vibration
work at instllation
• Insufficient strength of
mounting face
➁ Defective product
• Before/after shipping from
factory
➂ Improper adjustment during
commissioning
• Excess/shortage of
refrigerant, etc.
Note: