134
-
'11 • SCM-SM-110
Error code
Remote controller:
LED Green Red
Content
Indoor
Keeps flashing
Stays OFF
E58
Current safe stop
Model SCM40, 45, 50, 60, 71, 80
Outdoor
3
times ash
Error code
Remote controller: E58
LED Green Red
Indoor
Outdoor
Content
Current safe stop
(Model SRC40 - 60)
Keeps flashing
Stays Off
3 time flash
1. Applicable model
5. Troubleshooting
Model SCM40, 45, 50, 60, 71, 80
only
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air temp.
sensor
• Defective outdoor main PCB
Diagnosis Countermeasure
2. Error detection method
3.
Condition of Error displayed
4. Presumable cause
Note:
Is outdoor
ventilation condition
good ?
Inspect
outdor air temp.
sensor
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor main
PCB¡Replace.
(Defective outdor air temp.
sensor input circuit)
Inspect
compressor
YES
YES
YES
NO
NO
NO
NO
NO

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM71ZJ-S1 and is the answer not in the manual?

Mitsubishi SCM71ZJ-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSCM71ZJ-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals