32
-
'12 • SRK-T-130
'09•SRK-DB-087D
(6)ޓFlap and louver control
(a) Flap
(b) Louver
(c) Swing
(d) Memory flap (Flap or Louver stopped)
(e) When not operating
COOL , DRY, FAN
Remote control
display
HEAT
Approx. 5°
Approx. 25°
Approx. 25°
Approx. 40°
Approx. 35°
Approx. 50° Approx. 80°
Approx. 55°
Approx. 60°
Approx. 80°
Angle of Flap from Horizontal
Center installation
Remote control
display
Angle of Louver
Left Approx. 50° Left Approx. 20°
Center
Right Approx. 20° Right Approx. 50°
In HEAT operation In COOL, DRY, FAN operation
Approx. 35°
Approx. 80°
Approx.
Approx. 60°
(Swing)
(Flap stopped)
(Louver stopped)
(Swing)
(i) (ii)
(5) Selection of the annual cooling function
(a) The annual cooling function can be enabled or disabled by means
of the jumper wire (J172) on the indoor unit PCB and the dip switch
(SW2-4) on the interface kit (option) PCB.
Note: (1) Default states of the jumper wire (J172) and the interface kit at the shipping from factory On the
PCB, the dip switch (SW2-4) is set to enable the annual cooling function.
(2) To cancel the annual cooling setting, consult your dealer.
(b) Content of control
(i)
If the outdoor air temperature sensor (TH3) detects below 5°C, the indoor unit
speed is switched to 9th step. (It is not possible to change.)
(ii)
If the outdoor air temperature sensor (TH3) detects higher than 7°C, the indoor
unit speed is changed to the normal control speed.
Jumper wire
(J172)
Interface kit
(SC-BIKN-E)
SW2-4
Function
Shorted ON Enabled
Shorted OFF Disabled
Open ON Disabled
Open OFF Disabled
Jumper wire (J172)
ON
5 7
OFF
Outdoor air temperature ( C)