'18 • SRK-SM-259
-
10
-
Notes (1) When the outdoor heat exchanger temperature is in the range of B-C ºC, the speed is reduced by 8 rps at each 20 seconds.
(2) When the temperature is C ºC or higher, the compressor is stopped.
(3) When the outdoor heat exchanger temperature is in the range of A-B ºC, if the compressor speed is been maintained and the operation has
continued for more than 20 seconds at the same speed, it returns to the normal cooling operation.
Temperature list
SRK25, 35 SRK45
A B C A B C
Outdoor air temperature
>
=
32 ºC
53 58 63 48 53 55
Outdoor air temperature <
32 ºC
40 43 46 53 58 63
'09•SRK-DB-087D
(i) Operating conditions
(ii) Detail of operation:
CDAB
OFF
EF
Upper limit 50 rps
Lower limit 44 rps
ON
ON
Upper limit 50 rps
Lower limit 5044 rps
ON
Upper limit 60 rps
Lower limit 30 rps
Outdoor air temperature.(°C)
(iii) Reset conditions:
(f)
Heating high pressure control
(i) Purpose:
(ii) Detector:
(iii) Detail of operation:
A
B
C
D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
lower limit
speed 30 rps
(Example) Fuzzy
Temperature list
Models DXK09.12
ABCD
RPSmin < 50
50
<
=
RPSmin < 91
91
<
=
RPSmin < 97
97
<
=
RPSmin < 100
100
<
=
RPSmin < 115
115
<
=
RPSmin
First time
After the
second times
Outdoor air temperature (˚C)
ABCDEF
1)
2)
1)
2)
than 50
44<44> (30) rps, the speed is kept to 5044<44> (30) rps. However, when the thermo OFF, the
speed is
(Models DXK09, 12)
First time
After the
second times
Outdoor air temperature (˚C)
E FABCD
, E, F (Model DXK15)
(3) Values in
are for the model DXK15.
0
57
2
16
9
19
11
25
22
28
25
44
10
52
54.5
54 55
51.554.5
51.5 50
50
A
C
B
D
(f) Cooling low outdoor air temperature protective control
(e) Cooling low outdoor air temperature protective control
(i) Operating conditions
(ii) Detail of operation
CDAB
OFF
EF
Upper 2
Lower 2
ON
ON
Upper 3
Lower 3
ON
Upper 1
Lower 1
Outdoor air temperature (°C)
(iii) Reset conditions
(f ) Heating high pressure control
(i) Purpose
(ii) Detector
(iii) Detail of operation
A
B
C
D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
lower limit
speed 30(23) rps
(Example)
Compressor
speed
Temperature list
Models SRK20, 25, 35
ABCD
RPSmin < 50
50
<
=
RPSmin < 91
91
<
=
RPSmin < 97
97
<
=
RPSmin < 100
100
<
=
RPSmin < 115
115
<
=
RPSmin
First time
After the
second times
Outdoor air temperature (˚C)
ABCDEF
(Models SRK20-35)
First time
After the
second times
Outdoor air temperature (˚C)
ABCD
(Model SRK50)
9
16 19
11
Note (1) Value in ( ) are for the model SRK50.
When the outdoor air temperature (TH2) is 22°C or lower continues for 20 seconds while the compressor speed is other than 0 rps.
Compressor speed: Upper/lower limit (rps)
Lower 3Upper 2Lower 2
Lower 1
Range BRange A
Upper 1Upper 3
2624
Indoor air temperature ( Υ
)
50504430
50
Range A
Range B
445044
60
6027
Release
Release
50
SRK25, 35
SRK45
1) It controls the upper and lower limit values for the compressor speed according to the following table.
2) It checks the outdoor temperature (TH2) once every hour to judge the operation range.
When either of the following condition is satisfied.
1) The outdoor air temperature (TH2) is D°C or higher.
2) The compressor speed is 0 rps.
fanspeed fan
When the indoor heat exchanger temperature is in the range of A-B °C, if the compressor speed is been maintained and the operation has continued for more
than 20 seconds at the same speed, it returns to the normal heating operation.
B-C
C-D
48
48.5
48.5
48.5
48.5 - 40.1
40.1
53
56
56 - 52.5
52.5 - 50.8
50.8 - 42
42
55
58
58
58 - 56.2
56.2 - 47.3
47.3
58
61
61
61
61
61
'09•SRK-DB-087D
CDAB
OFF
EF
Upper limit 50 rps
Lower limit 44 rps
ON
ON
Upper limit 50 rps
Lower limit 5044 rps
ON
Upper limit 60 rps
Lower limit 3027 rps
Outdoor air temperature (°C)
(iii) Reset conditions
(g)
Heating high pressure control
(i) Purpose
(ii) Detector
(iii) Detail of operation
A
B
C
D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
-
-
-
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
lower limit
speed 30(35) rps
(Example) Fuzzy
Temperature list
Models DXK09.12
ABCD
RPSmin < 50
50
<
=
RPSmin < 91
91
<
=
RPSmin < 97
97
<
=
RPSmin < 100
100
<
=
RPSmin < 115
115
<
=
RPSmin
First time
After the
second times
Outdoor air temperature (˚C)
ABCDEF
1)
2)
(Models SRK25, 35)
First time
After the
second times
Outdoor air temperature (˚C)
E FABCD
, E, F (Model SRK45)
0
57
2
16
9
19
11
25
22
28
25
fan fan
speed
52
54.5
54 55
54.5-51.5
51.5-50 -
-
50--
10
2624
Indoor air temperature ( Υ
)
Range A
Range B