(5) Self-diagnosis table
When this air conditioner performs an emergency stop, the reason why the emergency stop occurred is displayed by the flashing of
display lights. If the air conditioner is operated using the remote control 3 minutes or more after the emergency stop, the trouble
display stops and the air conditioner resumes operation. 
(1)
When a heat exchanger sensor 1 wire disconnection is detected while 
operation is stopped. (If a temperature of –28ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) 
(Not displayed during operation.)
When a room temperature sensor wire disconnection is detected while 
operation is stopped. (If a temperature of –45ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) 
(Not displayed during operation.)
• Broken heat exchanger sensor 
1 wire, poor connector 
connection
• Broken room temperature 
sensor wire, poor connector 
connection
Heat exchanger 
sensor 1 error
Room 
temperature 
sensor error
When conditions for turning the indoor unit’s fan motor on exist during 
air conditioner operation, an indoor unit fan motor speed of 300 rpm or 
lower is measured for 30 seconds or longer. (The air conditioner stops.)
• Defective fan motor, poor 
connector connection
Indoor fan 
motor error
ON
1 time
flash
ON
2 time
flash
ON
6 time
flash
When an outdoor temperature sensor wire disconnection is detected 
while the power is turned on or after the outdoor unit’s speed has 
continued at 0rps or higher for 2 minutes. (If a temperature of –55ºC or 
lower is detected for 20 seconds, it is judged that wire is disconnected.) 
(The compressor is stopped.)
• Broken outdoor air temp. 
sensor wire, poor connector 
connection
Outdoor air 
temperature 
sensor error
1 time
flash
Keeps
flashing
When a heat exchanger sensor wire disconnection is detected while the 
power is turned on or after the outdoor unit’s speed has continued at 
0rps or higher for 2 minutes. (If a temperature of –55ºC or lower is 
detected for 20 seconds, it is judged that wire is disconnected.) 
(The compressor is stopped.)
• Broken heat exchanger sensor 
wire, poor connector 
connection
Outdoor heat 
exchanger 
sensor error
2 time
flash
Keeps
flashing
When a discharge pipe sensor wire disconnection is detected after the 
outdoor unit’s speed has continued at 0rps or higher for 10 minutes. (If 
a temperature of –25ºC or lower is detected for 20 seconds, it is judged 
that wire is disconnected.) 
(The compressor is stopped.)
• Broken discharge pipe sensor 
wire, poor connector 
connection
Discharge pipe 
sensor error
4 time
flash
Keeps
flashing
The inverter output current (compressor motor current) exceeds the set 
value during compressor start. 
(The air conditioner stops.)
• Compressor locking, open 
phase on compressor output, 
shortcircuit on power 
transistor, closed service valve
Current Cut
1 time
flash
ON
When there is an emergency stop caused by trouble in the outdoor unit, 
or the input current value is found to be lower than the set value.
 (The air conditioner stops.)
When the power transistor is judged breakdown while compressor 
starts.
(The compressor is stopped.)
• Broken compressor wire
• Compressor blockage
Trouble of 
outdoor unit
2 time
flash
ON
When the value of the discharge pipe sensor exceeds the set value. 
(The air conditioner stops.)
• Gas shortage, defective 
discharge pipe sensor, closed 
service valve
Over heat of 
compressor
ON
5 time
flash
6 time
flash
ON
When there is no signal between the indoor unit’s board and outdoor 
unit’s board for 10 seconds or longer (when the power is turned on), or 
when there is no signal for 7 minute 35 seconds or longer (during 
operation)(the compressor is stopped).
• Defective power supply, 
Broken signal wire, defective 
in/outdoor unit boards
Error of signal 
transmission
If the compressor motor’s magnetic pole positions cannot be correctly 
detected when the compressor starts. 
(The air conditioner stops.)
• Defective compressor
• Open phase on compressor
• Defective outdoor unit boards
Rotor lock
2 time
flash
2 time
flash
When the outdoor unit’s fan motor speed continues for 30 seconds or 
longer at 75 rpm or lower. (3 times) (The air conditioner stops.)
• Defective fan motor, poor 
connector connection
Outdoor fan 
motor error
7 time
flash
ON
Indoor unit display panel
Description
of trouble
Cause Display (flashing) condition
RUN 
light
TIMER
light
When the inverter command speed is lower than the set value and the 
current safe has operated. (the compressor stops)
• Overload operation
• Overcharge
• Compressor locking
Current safe 
stop
3 time
flash
—
—
—
8 time
flash
8 time
flash
8 time
flash
1 time
flash
2 time
flash
5 time
flash
6 time
flash
7 time
flash
ON
The wired remote control wire Y is open. The wired remote control 
wires X and Y are reversely connected. Noise is penetrating the wired 
remote control lines. The wired remote control or indoor control PCB is 
faulty. (The communications circuit is faulty.)
• Broken wired remote control 
wire, defective indoor unit 
boards
Error of wired 
remote control 
wiring
—
—
—
3 time
flash
ON
• Broken power transistor
Power 
transistor
error
4 time
flash
1 time
flash
ON
Outdoor
unit
LED
When a heat exchanger sensor wire 3  disconnection is detected while 
operation is stopped. (If a temperature of –28ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) 
(Not displayed during operation.)
• Broken heat exchanger sensor 
3 wire, poor connector 
connection
Heat exchanger 
sensor 3 error
ON
3 time
flash
—
E 16
E 38
E 37
E 39
E 42
E 59
E 36
E 5
E 3
E 60
E 47
E 48
E 35
E 1
E 58
E 51
Wired 
remote 
control 
display
When the value of the outdoor heat exchanger sensor exceeds the set 
value.
• 
Overload operation, overcharge
• Broken outdoor heat exchange 
sensor wire
• Closed service valve
Cooling high 
pressure 
protecton
Keeps
flashing
ON
2 time
flash
When the wrong voltage connected for the power supply.
When the outdoor control PCB is faulty.
• Defective active filter
Active filter 
voltage error
ON
5 time
flash
2 time
flash
—
—
—
Notes (1)The air conditioner cannot be restarted using the remote control for 3 minutes after operation stops.