51
Part name Check method and criterion
Measure the resistance using a tester.
(Part temperature : -10°C ~ 40°C)
Defrost thermistor (RT62)
Outdoor heat exchanger
temperature thermistor
(RT68)
Normal abnormal
5kΩ ~ 55kΩ
Open or short-circuit
Normal abnormal
100kΩ ~ 250kΩ
Opened or short-circuit
Normal abnormal
2.6kΩ ~ 3.3kΩ
Open or short-circuit
Normal
abnormal
0.40Ω ~ 0.49Ω
Open or short-circuit
Measure the resistance using a tester, after warming up the thermistor by holding by hand.
(Part temperature : 20°C ~ 40°C)
Discharge temperature
thermistor (RT61)
Measure the resistance between terminals using a tester.
(Winding temperature : -10°C ~ 40°C)
Compressor (MC)
Measure the resistance between lead wires using a tester.
(Part temperature : -10°C ~ 40°C)
Outdoor fan motor (MF)
Measure the resistance using a tester. (Part temperature : -10°C ~ 40°C)
R. V. coil (21S4)
Measure the resistance using a tester.(Part temperature : -10°C ~ 40°C)
Expansion valve (LEV)
Color of lead wire
Normal
WHT - RED
RED - ORN
YLW - BRN
BRN - BLU
Abnormal
Open or
short-circuit
37.4Ω ~ 53.9Ω
SUZ-A18VR.TH
SUZ-A24VR.TH
Normal
RED - BLK
BLK - WHT
WHT - RED
Open or
short-circuit
(Not including
WHT - ORN)
13.4Ω ~ 16.4Ω
abnormal
Color of
lead wire
Normal abnormal
25kΩ ~ 100kΩ
Open or short-circuit
Measure the resistance using a tester.
(Part temperature : 10°C ~ 40°C)
Fin temperature thermistor
(RT65)
12-2-2. Trouble criterion of main parts (2)
OC304A --2qxp 04.6.29 8:34 AM Page 51