Contents
A Introduction 2
B Product Range 3
C Product Specification 4
D Standards Compliance 6
E Safety Instructions 6
F Installation - General Notes 8
G Installation 10
H Testing 11
I Tripping in Service 14
J Guarantee 15
Please leave this leaflet with the
end user for future reference
52778PL Rev BB
2
ln this range of Single Module Width RCBO’s, each
product provides dual protection; from Over-current via
its MCB section, and from Earth Leaking Fault Current
(Residual Current) via its RCD section.
These devices provide RCD protection in full
compliance with the requirements of the Standard
BS EN 61009-1. They also provide very effective RCD
protection in the Supply Voltage Range of 110 V to
253V a.c., meeting the requirements of the Standard
for sensitivity and trip speed at
n
and 2
n
.
They meet the requirement of the current edition of the
UK Wiring Regulations (BS 7671), as regards ability to
trip with Earth Loop Impedance of up to 1667 Ω (for a
30mA RCD), by being able to operate with Earth Loop
Impedance of up to 10,000 Ω.
A. INTRODUCTION
5
Mechanical
Terminal Capacity Line in - 25mm
2
Line and Neutral out - 25mm
2
Product Width 18mm
Product Height above 76mm
Din Rail
Product Length 118mm
Suitable Mounting MK Sentry Consumer Unit
Enclosure (select from the MK range)
Method of Mounting Top Hat Mounting (DIN)
in Enclosure Rail to EN 50022
Environmental
Ambient Temperature Range
-
5°C to +40°C
Storage Temperature Range
-
30°C to +85°C
Protection, Un-installed Device IP 20
Protection, Installed in the
Consumer Unit IP 40
C. PRODUCT SPECIFICATION (Cont.)
6
The products in this range comply with the requirements of the
following standards:
BS EN 61009-1
BS IEC 61009-2-2
EN 61543 for EMC
D. STANDARDS COMPLIANCE
1. This product must be installed by a competent person (e.g. a
qualified electrician) in accordance with these instructions and
the appropriate clauses of the current edition of the IEE Wiring
Regulations (BS7671) and Building Regulations.
2. The RCBO must be installed within a SENTRY
®
Consumer Unit
(select from the range of MK consumer units).
3. The RCBO should not be regarded as a substitute for basic safety
precautions.
4. Test the RCBO quarterly, as detailed in the current edition of the IEE
Wiring Regulations (BS 7671), by pressing the TEST BUTTON marked
T, provided on the product (see label on the Consumer Unit).
E. SAFETY INSTRUCTIONS
7
Do not use the product if
it fails to trip during this
operation. Failure to trip
indicates either no supply to
the RCBO or a faulty device.
Consult a qualified electrician
or contact MK Technical Sales
and Service Department.
Telephone:
01268 563720
(National)
+44 (0) 1268 563758 (International)
5. Choose an RCBO from TABLE 1,
with the correct ratings, for the
circuit to be protected.
6. The RCBO’s in this range must
not be used in ambient
temperatures outside their
specified range.
L
IN
N
OUT
L
O
UT
I
n 30mA
6000
3
230V
B32
7936s
ON
BS EN61009-1
Load
N
OUT
L
OUT
N
IN-Supply
(Blue)
FE
(White)
L
IN-Supply
Blue Flying
Curled Neutral
Supply Lead
White or
Cream
Flying Earth
Supply Lead
Line Supply
E. SAFETY INSTRUCTIONS (Cont.)
8
1. The RCBO shall be installed at the source of the circuit
in which the Earth Fault and Over-current protection is
required.
2. The RCBO’s may be installed alongside other SENTRY
®
Modular Products, as part of a larger assembly.
3. The RCBO is a sensitive device designed for fixed
installation in a clean and dry environment. The device
must not be installed as part of a portable system which
may be subject to mechanical shocks and vibration.
4. An adhesive label giving test instructions is provided
with each RCBO. This label shall be placed in a
prominent position close to the RCBO (preferably on the
Consumer Unit Cover).
5. Upon completion of the installation, please leave this
instruction leaflet in close proximity to the RCBO, for
future reference.
F. INSTALLATION - GENERAL NOTES
4
Electrical
Number of Poles Single Pole with Solid
Neutral
Rated Supply Voltage 230V a.c. +10%,
-
15%
Supply Voltage Range 110 V to 253V a.c.
Supply Frequency Range 45 to 66Hz
Supply Voltage Range for 195V to 253V a.c.
Test Device Operation
RCD Trip Current Rating 30 mA
Operating Characteristics Type AC
MCB Type B, C
Rated Short Circuit 6 kA
Capacity Icn
Neutral Connection Flying Lead
Earth Connection Flying Lead
C. PRODUCT SPECIFICATION
3
The product range is given in Table 1 below.
All products in the range have an RCD trip current
rating of 30mA.
Table 1
Type B RCBO Type C RCBO
List No. MCB Current List No. MCB Current
Rating A Rating A
07932s 6 08932s 6
07933s 10 08933s 10
07934s 16 08934s 16
07935s 20 08935s 20
07936s 32 08936s 32
07937s 40 08937s 40
07938s 45 08938s 45
07939s 50 08939s 50
B. PRODUCT RANGE
Figure 1
Question and Answer IconNeed help?

Do you have a question about the MK SENTRY RCBO and is the answer not in the manual?

MK SENTRY RCBO Specifications

General IconGeneral
BrandMK
ModelSENTRY RCBO
CategoryOther
LanguageEnglish

Summary

Introduction to Sentry RCBO

Sentry RCBO Product Range

Sentry RCBO Product Specification

Electrical Specifications

Details electrical parameters including voltage, frequency, RCD trip current, MCB types, and short circuit capacity.

Mechanical Specifications

Covers terminal capacity, product dimensions, and mounting requirements.

Environmental Specifications

Outlines operating and storage temperature ranges and protection ratings for the device.

Sentry RCBO Standards Compliance

Sentry RCBO Safety Instructions

Critical Safety Warning: Failure to Trip

Instructions for handling product failure to trip, emphasizing professional consultation.

Sentry RCBO Installation General Notes

Sentry RCBO Installation Procedure

Installation Torque and Labeling

Specifies terminal screw torque values and affixing of test instruction labels.

Sentry RCBO Testing Procedures

Insulation Resistance Tests

Procedure for insulation resistance testing, requiring disconnection of loads.

RCD Tester Calibration Checks

Details required trip times for specific test currents using a calibrated RCD tester.

Sentry RCBO Tripping in Service

Sentry RCBO Guarantee Information