77BS-Device Supervisor Object 7BChapter Four: Operation
82
S-Device Supervisor Object Supported Services
The S-Device Supervisor Object is supported by the seven DeviceNet services listed in Table 49.
Refer to Supported Service Summary, page 103, for more information.
Table 49: S-Device Supervisor Object Supported Services
Service
ID #
(hex)
Service
Name
Parameter
Data
Type(s)
Service
Type Description
05 Reset* USINT Request Places the object into its Initializing
state.
06 Recover*
(start)
none Request Causes the device to transition from
the Abort state to the Operating
state.
07 Abort*
(stop)
none Request Places the device in its Abort state.
0E Get_Attribute_Single* USINT Request Reads the object attribute.
10 Set_Attribute_Single* USINT,
Attribute
Data Type
Request Modifies the object attribute.
4D Lock none Request Restricts access to Read-Only
attributes. Places the device into the
User Mode.
4E Unlock
(Password Protected)
UINT Request Makes Read-Only attributes
modifiable and places the device
into Calibration Mode.
* DeviceNet common services.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MKS Baratron DMA Series and is the answer not in the manual?

MKS Baratron DMA Series Specifications

General IconGeneral
BrandMKS
ModelBaratron DMA Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals